Configuration of the SGX 5150 Lantronix Wi-Fi controller

Valid from build 2018.????

Introduction

This document is a guide to the configuration of the SGX 5150 Lantronix Wi-Fi controller typically used on newer picking trolleys. The basic network/Wi-Fi configuration is covered by the SGX 5150 Quick Start Guide and the SGX 5150 User Guide. The configuration of the serial connection to the controller and the Logisoft related network specifics are covered below.

Initial controller connection and logon

Connect to the controller from a browser using the configured IP-address

Browser login

If the default user/password is not changed during the network configuration above, you should use

username: admin
password: PASS

Configuration of the controller

The configuration consists of two steps

Line configuration

Choose the ‘Administration’ tab and select ‘Line 1’ in the ‘Line’ menu.
Set the ‘Name’, ‘Baud Rate’, ‘Gap Timer’ and ‘Threshold’ as shown below.

Line 1 configuration

Once configured press the ‘Submit’ button

Line 1 after submit

Tunnel configuration

Select ‘Tunnel 1’ in the ‘Tunnel’ menu

Choose the ‘Serial Settings’ just to validate that the serial connection values are correct.
They should match the values configured under ‘Line 1’, as ‘Tunnel 1’ and ‘Line 1’ are implicitly tied together.

Tunnel 1 Serial Settings

Next choose ‘Packing Mode’ and set the values as shown below.

Tunnel 1 Packing Mode

Press ‘Submit’ to save the values.

Tunnel 1 Packing Mode after submit

Choose ‘Accept Mode’ and check the values. Change if necessary according to the values below.
The ‘Local Port’ is the prot that Logisoft will use to communicate TO the controller. Press ‘Submit’ if values are changed.

Tunnel 1 Accept Mode

Choose ‘Connect Mode’ and check the values. Change if necessary according to the values below.

Tunnel 1 Connect Mode

Click the ‘<none>’ value of ‘Host 1’ to activate the dialog to setup the IP address and port values.

Tunnel 1 Connect Mode

The values ‘Local Port’, ‘Address’, ‘Port’ and ‘Protocol’ are important and especially ‘Local Port’, ‘Address’, ‘Port’ must be set to match the settings in Logisoft

Tunnel 1 Connect Mode submit
The result afte ‘Submitting’

Logisoft Setup

Below the values are shown which must be set to match the values of the SGX 5150 controller

Logisoft setup

Below a picture of a picking trolley is shown

Trolley example

This is where the controller ID can be found

Trolley Controller ID